InStAllAtIOn

troubleshooting

14. troubleshooting

Note

The high limit safety cut-out can respond at temperatures

below –15 °C. The appliance may be subjected to these

temperatures during storage or transport.

Fault

Cause

Remedy

The water does not

heat up.

The high limit safety

cut-out has responded

because the controller is

faulty.

Remedy the cause of the

fault. Replace the control-

ler-limiter combination.

The high limit safety cut-

out has responded be-

cause the temperature has

dropped below -15 °C.

Press the reset button.

A heating element is

faulty.

Replace the flanged im-

mersion heater.

The safety valve drips

when the heating is

switched off.

The valve seat is contam-

inated.

Clean the valve seat.

26

�0

2�

09

�0

07

0�

1

1 High limit safety cut-out reset button

15. maintenance

WARNING Electrocution

Carry out all electrical connection and installation work

in accordance with relevant regulations.

WARNING Electrocution

Before any work on the appliance, disconnect all poles

of the appliance from the power supply.

If you need to drain the appliance, observe chapter "Draining the

appliance".

15.1 checking the safety valve

f

f Regularly vent the safety valve on the safety assembly until a

full water jet is discharged.

15.2 draining the appliance

WARNING Burns

Hot water may escape during the draining process.

If the cylinder needs to be drained for maintenance or to protect

the whole installation when there is a risk of frost, proceed as

follows:

f

f Close the shut-off valve in the cold water line.

f

f Open the hot water taps on all draw-off points.

f

f Drain the appliance via the safety assembly.

15.3 replacing the signal anode

f

f Replace the signal anode if it becomes depleted.

15.4 cleaning and descaling the appliance

f

f Never use descaling pumps.

f

f Only descale the flanged immersion heater after dismantling

and never treat the cylinder surface or protective anode with

descaling agents.

Torque of the flange screws: see chapter "Specification / Dimen-

sions and connections"

15.5 replacing flanged immersion heater

26

�0

2�

09

�0

06

9�

5

6

4

2

3

1

1 Insulation plate

2 Flange plate

3 Soldered flange

4 Insulating plate

5 Corrosion resistor 390 Ω

6 Gasket
The corrosion resistor acts to balance the potential and prevents

power leakage corrosion on the heating elements.

f

f Never damage or remove the corrosion resistor during

maintenance.

f

f After replacing the corrosion resistor, reassemble the flanged

immersion heater correctly.