Smart board, Light identification, Troubleshooting chart light # description – Grain Systems PNEG-377 User Manual

Page 68

Advertising
background image

68

Fan And Heater

Light Identification

Light 1

Signifies the on/off switch is on

and the heater hi-limit is good.

Light 2

Signifies the fuse is good.

Light 3

Signifies the 10 second time delay

relay and/or the DPDT relay is

energized.

Light 4

Signifies the vapor hi-limit is

closed, or set, not tripped out.

Light 5

Signifies the humidistat-thermostat

is calling for heat.

Light 6

Signifies the DPDT relay, vapor

solenoid, liquid solenoid, ignition

transformer and indication light are

receiving power.

Light 7

Signifies the cycle thermostat is

closed and the cycle solenoid is

receiving power.

Light A

Signifies the flame probe is closed.

Light B

Signifies the DPDT relay is

energized and the time delay reset

is receiving power.

Troubleshooting Chart

Light #

Description

0

If no light is on, first check the on/

off switch to be sure it is in the on

position. If the unit still does not

operate, check the heater hi-limit.

1

If light #1 is the only one lit,

check the fuse on the SMART

BOARD. If faulty, replace.

1 and 2

If only lights 1 and 2 are lit,

check your connections to the

flame detection module. (blue/

black and white/brown wires). If

connection is good replace flame

detection module.

1,2 and A

If onlylights 1,2 and A are lit,

check the 10 second purge relay

and/or the DPDT relay. Replace

either part if faulty and restart

unit.

1,2,3 and A

If only lights 1,2,3 and A re lit

the vapor hi-limit has shut down

the unit. If the unit has been

operating and just shut down,

allow time for the vapor high

limit to cool down (2 or 3

minutes). The vapor hi-limit

will automatically reset itself.

Then, readjust the vaporizer to a

cooler position and the unit will

restart itself. If it will not restart

check and/or replace vapor hi-

limit.

1,2,3,4 and A If only lights 1,2,3,4 and A are

lit, the humidistat thermostat or

other heater control device has

shut down the unit. Allos time

for thermostat to cool and if unit

does norestart check and/or

replace control device.

1-5 and A

If only lights 1-5 and A are lit

the time delay reset has shut

down the unit. Reset the delay

and restart the unit. If the delay

connot be reset then replace. (If

reset keeps kicking out flame

sensor may be bad or need to be

adjusted into the flame).

1-6, A and B Check to see that spark plug is

giving good blue sparkplug is

giving good blue spark. If spark

plug is not sparking check

transformer, spark plug and

spark plug wire. If unit does

have good spark check to be sure

that gas supply is on.

SMART BOARD