Operating voltage

100-240 VAC / 50-60 Hz

(DC operation permissible)

Supply connection

L, N (PE not required)

Control connections

DALI IEC 62386, a maximum of 10

electronic ballasts can be connected,

max. line length 100 m

Pushbutton input

Potential-free make contact, max. line

length 50 m

Sensor connection

Max. 2 sensors, max. line length

25 m

Pin assignment:

1: Supply voltage (+ 3.3 V)

2: Light measurement

3: Motion signal

4: Ground

Max. load contact load

capacity L’

5 A resistive load
Max. number of ECGs: 10 (depends

on the ECG type to be connected)

Fuse

External 16 A

Power consumption

Operation: 1 W

Standby: < 0.5 W

Ambient temperature

0 °C … +50 °C

Adjustable light value

20-600 lux (measured at sensor)

Protection type

IP 20

Protection class

II

Dimensions

(L x W x H)

118 x 30 x 21 mm

Hole distance for

mounting

110 mm

The CE requirements to EN 60928 are fulfilled. The EMC requi-

rements to EN 61547 are fulfilled.

Conformity with the relevant EU directives is

confirmed by the CE symbol.

Connecting the control unit

Left: Individual operation with max. 2 sensors
Right: Networked operation with up to 4 DALI MULTIeco control

units and central presence detection
H Sensor
J Pushbutton
K Lamp
L Y-Connector
M Y-Connector Screw
N To luminaire group 1
O To luminaire group 2

1 2 3 4

1 2 3 4

L

N

J

N

L

N

Sensor

DALI MULTIeco

J

O

L

N

Sensor

DALI MULTIeco

H

M

L

H

L

J

K

L

N

L‘

DA+

DA -

DA

DA

~

~

DA

DA

~

~

Sensor

DALI MULTIeco

QTi DALI EVG

QTi DALI EVG

N

PE

K

H

1 2 3 4

Pin