3 profibus warning word, B-53 profibus, Warning word – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 100: Fault code, Pb-47 fault number

Advertising
background image

PB-44 Fault Message Counter

Range:

Function:

capacity is eight error events. The buffer and

counter are set to 0 upon reset or power-up.

PB-45 Fault Code

Range:

Function:

0

*

[0 - 0] This buffer contains the alarm word for all alarms

and warnings that have occurred since last reset or

power-up. The maximum buffer capacity is eight

error events.

PB-47 Fault Number

Range:

Function:

0

*

[0 - 0] This buffer contains the alarm number (e.g. 2 for

live zero error, 4 for mains phase loss) for all alarms

and warnings that have occurred since last reset or

power-up. The maximum buffer capacity is eight

error events.

PB-52 Fault Situation Counter

Range:

Function:

0

*

[0 - 1000] This parameter displays the number of error

events which have occurred since last reset of

power-up.

PB-53 Profibus Warning Word

Range:

Function:

0

*

[0 - 65535] This parameter displays Profibus communication

warnings. Refer to the Profibus Operating

Instructions for further information.

Read only

Bit

Meaning

0

Connection with DP-master is not ok

1

Not used

2

(Network Data link Layer) is not ok

3

Clear data command received

4

Actual value is not updated

5

Baudrate search

6

PROFIBUS ASIC is not transmitting

7

Restore of PROFIBUS is not ok

8

Frequency converter is tripped

9

Internal CAN error

10

Wrong configuration data from PLC

11

Wrong ID sent by PLC

12

Internal error occured

13

Not configured

14

Timeout active

15

Warning 34 active

Table 3.26

PB-63 Actual Baud Rate

Option:

Function:

This parameter displays the actual

Profibus baud rate. The Profibus

Master automatically sets the baud

rate.

[0]

9,6 kbit/s

[1]

19,2 kbit/s

[2]

93,75 kbit/s

[3]

187,5 kbit/s

[4]

500 kbit/s

[6]

1500 kbit/s

[7]

3000 kbit/s

[8]

6000 kbit/s

[9]

12000 kbit/s

[10]

31,25 kbit/s

[11]

45,45 kbit/s

[255]

*

No baudrate found

PB-64 Device Identification

Range:

Function:

0

*

[0 - 0] This parameter displays the device identification.

Refer to the Operating Instructions for Profibus, for

further explanation.

PB-65 Profile Number

Range:

Function:

0

*

[0 - 0] This parameter contains the profile identification.

Byte 1 contains the profile number and byte 2 the

version number of the profile.

NOTE

This parameter is not visible via keypad.

PB-67 Control Word 1

Range:

Function:

0

*

[0 - 65535] This parameter accepts the Control Word from a

Master Class 2 in the same format as PCD 1.

PB-68 Status Word 1

Range:

Function:

0

*

[0 - 65535] This parameter delivers the Status Word for a

Master Class 2 in the same format as PCD 2.

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

99

3

3