AN-50 Terminal 42 Output

Option:

Function:

Current, then the setting of AN-52 Terminal 42

Output Max Scale must be:

Imotor x 100%/Imax = 22 A x 100%/38.4 A =

57%

[104] Torque rel

to limit

The torque setting is related to setting in

F-40 Torque Limiter (Driving)

[105] Torq relate

to rated

The torque is related to the motor torque

setting.

[106] Power

Taken from P-07 Motor Power [kW].

[107] Speed

Taken from F-53 Maximum Reference. 20 mA =

value in F-53 Maximum Reference

[108] Torque

Torque reference related to 160% torque.

[109] Max Out

Freq

0 Hz = 0 mA,F-03 Max Output Frequency 1 =

20 mA.

[113] PID

Clamped

Output

[119] Torque %

lim

Torque% lim: Torque reference. F-50 Reference

Range [Min - Max] 0% = 0 mA; 100% = 20 mA

F-50 Reference Range [-Max - Max] -100% = 0

mA; 0% = 10 mA; +100% = 20 mA

[130] Output

freq.

4-20mA

0 Hz = 4 mA, 100 Hz = 20 mA

[131] Reference

4-20mA

F-50 Reference Range [Min-Max] 0% = 4 mA;

100% = 20 mA

F-50 Reference Range [-Max-Max] -100% = 4

mA; 0% = 12 mA; +100% = 20 mA

[132] Feedback

4-20mA

Feedback 4-20 mA: F-50 Reference Range [Min-

Max] 0% = 4 mA; 100% = 20 mA

F-50 Reference Range [-Max-Max] -100% = 4

mA; 0% = 12 mA; +100% = 20 mA

[133] Motor cur.

4-20mA

Value is taken from DR-37 Drive Max. Current.

Inverter max. current (160% current) is equal

to 20 mA.

[134] Torq.% lim

4-20 mA

The torque setting is related to setting in

F-40 Torque Limiter (Driving).

[135] Torq.%

nom

4-20mA

The torque setting is related to the motor

torque setting.

[136] Power

4-20mA

Taken from P-07 Motor Power [kW]

[137] Speed

4-20mA

Taken from F-53 Maximum Reference. 20 mA =

Value in F-53 Maximum Reference.

[138] Torque

4-20mA

Torque reference related to 160% torque.

[139] Bus ctrl.

0-20 mA

An output value set from Network process

data. The output will work independently of

internal functions in the frequency converter.

AN-50 Terminal 42 Output

Option:

Function:

[140] Bus ctrl.

4-20 mA

An output value set from Network process

data. The output will work independently of

internal functions in the frequency converter.

[141] Bus ctrl

0-20mA t.o.

H-74 Warning Reference Low defines the

behaviour of the analog output in case of bus

time-out.

[142] Bus ctrl

4-20mA t.o.

H-74 Warning Reference Low defines the

behaviour of the analog output in case of bus

time-out.

[149] Torque %

lim 4-20mA

Analog output at zero torque = 12 mA.

Motoric torque will increase the output

current to max torque limit 20 mA (set in

F-40 Torque Limiter (Driving)).

Generative torque will decrease the output to

torque limit Generator Mode (set in

F-41 Torque Limiter (Braking))

Ex: F-40 Torque Limiter (Driving): 200% and

F-41 Torque Limiter (Braking): 200%. 20 mA =

200% Motoric and 4 mA = 200% Generatoric.

Illustration 3.33

[150] Max Out Fr

4-20mA

0 Hz = 0 mA, F-03 Max Output Frequency 1 =

20 mA.

AN-51 Terminal 42 Output Min Scale

Range:

Function:

0 %

*

[0 - 200

%]

Scale for the minimum output (0 or 4 mA) of

the analog signal at terminal 42.

Set the value to be the percentage of the full

range of the variable selected in

AN-50 Terminal 42 Output.

AN-52 Terminal 42 Output Max Scale

Range:

Function:

100

%

*

[0 -

200 %]

Scale the maximum output of the selected

analog signal at terminal 42. Set the value to

the maximum value of the current signal output.

Scale the output to give a current lower than 20

mA at full scale; or 20 mA at an output below

100% of the maximum signal value. If 20 mA is

the desired output current at a value between 0

- 100% of the full-scale output, program the

percentage value in the parameter, i.e. 50% = 20

mA. If a current between 4 and 20 mA is desired

at maximum output (100%), calculate the

percentage value as follows:

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C