F-08 Decel Time 1

Range:

Function:

corresponds to 0.01 s in speed mode. See accel

time in F-07 Accel Time 1.

Par

.

F

− 08 =

tdec

s

x

ns

RPM

ref

RPM

F-09 Torque Boost

Range:

Function:

100 %

*

[0 - 300

%]

Enter the % value to compensate voltage in

relation to load when the motor is running at

low speed and obtain the optimum U/f

characteristic. The motor size determines the

frequency range within which this parameter

is active.

Motor size

Change over

0.25 kW-7.5 kW

<10 Hz

Illustration 3.5 Changeover

3.3.2 F-1# Fundamental 1

Parameters to configure drive electronic overload and
high/low speed limits.

F-10 Electronic Overload

Option:

Function:

Thermal motor protection can be

implemented using a range of techniques:

•

Via a PTC sensor in the motor

windings connected to one of the

analog or digital inputs (F-12 Motor

Thermistor Input). See 3.3.3.1 PTC

Thermistor Connection.

•

Via a KTY sensor in the motor

winding connected to an analog

F-10 Electronic Overload

Option:

Function:

input (H-96 KTY Thermistor Input).

See 3.3.3.2 KTY Sensor Connection.

•

Via calculation of the thermal load,

based on the actual load and time.

The calculated thermal load is

compared with the rated motor

current I

M,N

and the rated motor

frequency f

M,N

. See 3.3.3.3 Electronic

Thermal Overload.

•

Via a mechanical thermal switch

(Klixon type). See 3.3.3.4 Klixon.

For the North American market: The

electronic overload functions provide class

20 motor overload protection in accordance

with NEC.

[0]

*

No

protection

Continuously overloaded motor, when no

warning or trip of the frequency converter is

required.

[1]

Thermistor

warning

Activates a warning when the connected

thermistor or KTY-sensor in the motor reacts

in the event of motor over-temperature.

[2]

Thermistor

trip

Stops (trips) frequency converter when

connected thermistor or KTY sensor in the

motor reacts in the event of motor over-

temperature.

The thermistor cut-out value must be > 3

k

Ω.

Integrate a thermistor (PTC sensor) in the

motor for winding protection.

[3]

Elec. OL

Warning 1

Calculates the load when set-up 1 is active

and activates a warning on the display when

the motor is overloaded. Program a warning

signal via one of the digital outputs.

[4]

Elec. OL Trip

1

Calculates the load when set-up 1 is active

and stops (trips) frequency converter when

the motor is overloaded. Program a warning

signal via one of the digital outputs. The

signal appears in the event of a warning

and if the frequency converter trips (thermal

warning).

[5]

Elec. OL

Warning 2

[6]

Elec. OL Trip

2

[7]

Elec. OL

Warning 3

[8]

Elec. OL Trip

3

[9]

Elec. OL

Warning 4

Parameter Descriptions

AF-650 GP Programming Guide

DET-618C

33