3.10 O-##

Options/Comms

Parameter group related to communications and options.

3.10.1 O-0# General Settings

Parameters to configure the general settings for communi-
cations and options.

O-01 Control Site

Option:

Function:

The setting in this parameter overrides

the settings in O-50 Coasting Select to

O-56 Preset Reference Select.

[0]

*

Digital and

ctrl.word

Control by using both digital input and

control word.

[1]

Digital only

Control by using digital inputs only.

[2]

Controlword only

Control by using control word only.

O-02 Control Word Source

Option:

Function:

NOTE

This parameter cannot be adjusted while
the motor is running.

Select the source of the control word: one of

two serial interfaces or four installed options.

During initial power-up, the frequency converter

automatically sets this parameter to [3] Option A

if it detects a valid fieldbus option module

installed in slot A. If the option is removed, the

frequency converter detects a change in the

configuration, sets O-02 Control Word Source

back to default setting RS-485, and the

frequency converter trips. If an option is

installed after initial power-up, the setting of

O-02 Control Word Source does not change, but

the frequency converter trips and displays:

Alarm 67 Option Changed.

When retrofitting a bus option into a frequency

converter, that did not have a bus option

installed to begin with, take an ACTIVE decision

to move the control to Bus based. This is done

for safety reasons to avoid an accidental

change.

[0]

None

[1]

Drive

RS485

[2]

Drive

USB

[3]

*

Option A

[4]

Option B

O-03 Control Word Timeout Time

Range:

Function:

1 s

*

[0.1 -

18000 s]

Enter the maximum time expected to pass

between the reception of two consecutive

messages. If this time is exceeded, it indicates

that the serial communication has stopped.

The function selected in O-04 Control Word

Timeout Functionis then carried out. A valid

control word triggers the time-out counter.

O-04 Control Word Timeout Function

Select the time-out function. The time-out function activates

when the control word fails to be updated within the time

period specified in O-03 Control Word Timeout Time.

Option:

Function:

[0]

*

Off

Resumes control via serial bus (fieldbus or

standard) using the most recent control

word.

[1]

Freeze output Freezes output frequency until communi-

cation resumes.

[2]

Stop

Stops with auto restart when communi-

cation resumes.

[3]

Jogging

Runs the motor at JOG frequency until

communication resumes.

[4]

Max. speed

Runs the motor at maximum frequency

until communication resumes.

[5]

Stop and trip

Stops the motor, then resets the frequency

converter to restart: via the fieldbus, via

[Reset], or via a digital input.

[7]

Select setup 1 Changes the set-up upon reestablishment of

communication following a control word

time-out. If communication resumes after a

time-out, O-05 End-of-Timeout Function

defines whether to resume the set-up used

before the time-out, or to retain the set-up

endorsed by the time-out function.

[8]

Select setup 2 See [7] Select setup 1

[9]

Select setup 3 See [7] Select setup 1

[10]

Select setup 4 See [7] Select setup 1

[26]

Trip

NOTE

To change the set-up after a time-out, the following
configuration is required:
Set K-10 Active Set-up to [9] Multi set-up and select the
relevant link in K-12 This Set-up Linked to.

O-05 End-of-Timeout Function

Option:

Function:

Select the action after receiving a valid

control word following a time-out. This

parameter is active only when O-04 Control

Parameter Descriptions

AF-650 GP Programming Guide

86

DET-618C

3