Step

Action

3.

Attach signal wiring from the fan shelf to the alarm card in the converter shelf immediately

above the fan shelf.

Figure 17 Alarm Wiring for Fan Shelf

4.

Attach de-energized DC cabling (typically 14 AWG) as shown here. Use ring lugs or alternate

per local practice. Fuse externally at 5 Amps. Note: Returns for the A and B feeds are shared

on the -48Vdc RTN. The lowest position on the terminal block is to provide frame ground for

the fan shelf. Power feeds should be derived from a fuse or breaker panel using discrete

cabling which is independent from the converter shelf.

Figure 18 DC Cabling Fan Trays in CPS3200U Systems