GE Industrial Solutions CPS3200U User Manual

Page 28

Advertising
background image

CPS3200U Upstream System – 23” Product Manual

CPS3200U

CC848779826 r09 December 2013

28

7 Inspect the Network - Check and Mark Wiring

Compliance

The CPS3200U +/-190V system is classified as an A2 circuit tested according to GR-1089-CORE Issue 3. As such, each

location in the network where the output is available to be touched must be protected and marked as an A2 voltage.

Step

Action

1.

Is accessibility to the circuit throughout the network consistent with A2 requirements?

2.

Is the 5-pin protector marked as a special circuit?

3.

Does the 5-pin protector protect each pair to a level corresponding to a CommScope

3C*EW Gas tube primary protector? This protector has a voltage breakdown range of

265-465 Volts and an impulse spark over range of <265-700 Volts. Protectors with a

lower voltage breakdown rating will be problematic.


To meet UL60950-21 specific procedural steps must be taken at the time of installation. This section goes through those

steps. These steps should be performed before power is distributed in the network. Normally the final step is performed

by closing the circuit using a 5-pin protector after DC power is applied to the system.

Step

Action

1.

Recognize that the Remote Feed Telecommunication Voltage limited (RFT-V) circuit is

voltage limited to +190V and -190V from ground.

2.

Is the total capacitance to ground on each line of the circuit less than 10μF?

The QS982A introduces 4.4μF. The remote electronics and line must introduce less than

5.6 μF of capacitance.

3.

Is the total capacitance line to line of the circuit less than 40μF?

The QS982A introduces 2.2μF. The remote electronics and line must introduce less than

37.2 μF of capacitance from tip to ring.

4.

Is the remote equipment also a RFT-V voltage limited circuit? Both ends of the circuit

must be designed to the same standard. This must be verified before the equipment is

connected together.

5.

Is the voltage rating of the Network Wiring sufficient to support 190V to ground?

6.

Is the chassis of the system bonded to ground? Verify by both observation and

measurement before powering the system. Measurement from the exterior of the

CPS3200U shelf to the cabinet ground bus should indicate continuity as determined via a

meter providing an audible beep or the standard method of continuity verification used in

the network.

Many network providers use a value of 10 ohms.

7.

Test each circuit by powering an open circuit at the remote end of the wire with a QS982

output. If red lights do not flash, there is no leakage path to ground at operating voltage.

If the FLT light does not blink yellow, there is no hard short between tip and ring.

Advertising