Galaxy Power System GPS4827

42

the address.

7.

Carefully attach the control unit to the connection unit using the ribbon
connector.

NOTE:

This connector/cable is not keyed, so be careful to line up the pins
properly.

8.

After approximately 1 minute, the green LED on the front of the module
will blink once approximately every 5 seconds. Detailed troubleshooting
information may be found in the User’s Guide for Millennium II Controller
Advanced Features manual.

Thermal Probes

Without thermal probes, many of the controller’s battery management features will
not function, or produce erroneous results. Some features requiring thermal inputs
are:

Slope Thermal Compensation

Reserve Time Prediction

High Temperature Alarm

Ambient High and Low Temperature Alarms

High Temperature Disconnect

Step

Action

NOTE:

The controller supports a number of thermal probe inputs. The type of
probe used determines where it is connected on the controller. Detailed
thermal probe and battery management information may be found in the
User’s Guide for Millennium II Controller Advanced Features manual.

1.

The following table shows the type of probe and connector location on the
Millennium:

Type of Probe

Comcode

Controller Connection
Location

10/30K

P3

210E Thermal Probe
Mux

P3

1 Wire Temperature
Monitoring Devices

P7

Terminal Block
Interface for 3
additional 10k probes
or 210E connection

TB2

Pin

Description

1

Probe 2

2

Probe 2 RTN

3

Probe 3