GE Industrial Solutions GPS4827 User Manual

Page 79

Advertising
background image

Galaxy Power System GPS4827

77

4.

Observe:

The plant voltage increases to the set voltage

Power Minor alarm (PMN) is generated

RECT and MIN LEDs are illuminated

5.

Using the Float Settings Menu Screens, select Set Point.

6.

Use the Arrows, and UP/DOWN keys to change the system float
voltage setpoint to it’s original value. Press ENTER to save.

7.

Observe:

The plant voltage decreases to the original set voltage

Power Minor alarm (PMN) retires

RECT and MIN LEDs are extinguished

High Float Voltage Alarm – Systems with Actual Loads

Step

Action for Testing the High Float Voltage Alarm

NOTE:

Clear all controller alarms for this test.

NOTE:

The System Voltage WILL NOT change.

NOTE:

The high float voltage alarm test is completed by changing the
threshold for this condition below the system voltage to make it
active.

1.

Using the Float Settings Menu Screens, select Set Point and note the
value. ________

2.

Using the Voltage Alarms Menu Screens, note the High Float Alarm
threshold value. _________

3.

Use the Arrows, and UP/DOWN keys to change the High Float Alarm
Threshold to 0.1V below the System Voltage. Press ENTER to save.

4.

Observe:

Power Minor alarm (PMN) is generated

RECT and MIN LEDs are illuminated

5.

Using the Voltage Alarms Menu Screens, change the High Float Alarm
threshold value to it’s original value. Press ENTER to save.

6.

Observe:

Power Minor alarm (PMN) retires

RECT and MIN LEDs are extinguished


High Voltage Shutdown – New Installations Only

STEP

Action for Testing High Voltage Shutdown Alarm

NOTE:

The High Voltage Shutdown Test is recommended only for new
installations where a dummy load is available prior to the application of
office load, and batteries are connected.

NOTE:

There are three requirements for a serial rectifier to shut down upon a
controller initiated High Voltage Alarm.

Advertising