Wiring alarm and control inputs – GE Industrial Solutions GPS4827 User Manual

Page 48

Advertising
background image

Galaxy Power System GPS4827

46

53

CTLRC

54

CTLRO

User Relay 2

55

UR2O

56

UR2C

57

UR2R

Very Low Voltage

58

VLVR

59

VLVC

60

VLVO



Wiring Alarm and Control Inputs

In a standard Galaxy Power System configuration, plant level alarms are sent to the
controller via the Bay Interface Card through serial data communication. The following
alarm inputs are provided for discretionary use in non-standard applications.

Table 9-C: Controller Alarm and Control Inputs

Alarm

Pin

Number

Signal Name

Low Voltage 2 Disconnect State Detect

61

LVD2

Fuse Alarm Major

63

FAJ

Fuse Alarm Minor

65

FAN

Auxiliary Alarm Major

64

AMJ

Auxiliary Alarm Minor

66

AMN

Timer Float Control

67

TFLT

Timer Boost Control

68

TBST

Plant Battery Test

71

PBT

Open String Detect

72

OS

Transfer Rectifier 1

73

TR1

General Purpose Input 4

74

IN-4 previously TEQ

General Purpose Input -5 (Previously

Engine Transfer)

75

IN-5 Previously ETR

Reserve Operation

77

RO

Transfer Rectifier 2

79

TR2

Transfer Rectifier 4

80

TR4

Reserve Battery-Emergency Power Off

81

RBRPO

General Purpose Input 1

82

IN-1

BTP or General Purpose Input 2

83

IN-2/BTP

Low Voltage 1 Disconnect State Detect

84

LVD1

Transfer Rectifier 3

85

TR3

General Purpose 4-20mA Measuring

87

4-20mA

Advertising