71

cell battery voltage as a function of
temperature.

Enabled

Enables

or

Disables

the

Thermal

Compensation Feature. Move the cursor to
the field and use the <+> or <-> key to Enable
or Disable. Press <ENTER> to save the
change.

High Temp
Comp

This

feature

allows

the

system

to

compensate for high temperatures.

Volt

Step

Down

Battery step temperature can be set from
113-185F. At this temperature, the system
voltage is reduced by 0.17 X # of cells/string.

High Comp
Limit

This sets the maximum temperature for
which thermal compensation is active.

Decrease

This sets the slope (mV/degC) for high
temperature compensation.

Nominal
Temp

This field set the temperature at which no
compensation is required. The system
voltage is at the setpoint float mode.

Low Temp Comp

This

feature

allows

the

system

to

compensate for low temperatures.

Low T Comp This enables or disables the low temperature

compensation feature.

Low Comp
Limit

This sets the minimum temperature for
which thermal compensation is active.

Increase

This sets the slope (mV/degC) for low
temperature compensation.

8.

Recharge Current
Limit

This feature sets the total amount of current
that will be allowed to recharge the batteries.

Limit

The configuration of this field enables or
disables the feature.

Limit to

This programmable value sets the maximum
amount of recharge current (in Amps) that
will be allowed for recharging the batteries.
The range is from 10 – 1000A.