Galaxy Power System GPS4827

89

13 Safety

Please read and follow all safety instructions and warnings before servicing the GPS 4827.
Reference the GPS Installation Guide and individual module product manuals for safety
statements specific to the modules.

Safety Statements

Please read and follow all safety instructions and warnings before installing,
maintaining, or repairing the system:

The CE Mark demonstrates compliance with the European Union Council
Directives for Low Voltage and EMC.

The UACD is Underwriters Laboratories (UL) recognized per Subject Letter 1801,
DC Power Distribution Centers for Telecommunications Equipment.

Install only in restricted access areas (dedicated equipment rooms, equipment
closets, or the like) in accordance with articles 110-26, 110-27, and 110-18 of
the U.S. National Electric Code (NEC-2011), ANSI/NFPA No. 70, and pursuant to
applicable local codes.

This equipment is to be used in controlled environments (an area where the
humidity is maintained at levels that cannot cause condensation on the
equipment, the contaminating dust is controlled, and the steady-state ambient
temperature is within the range specified).

This equipment has been evaluated for continuous use in ambient temperature
from 5°C to 55°C.

This equipment must not be installed over combustible surfaces.

For installations in the United States, Listed compression connectors are to be
used to terminate Listed field-wired conductors where required. For all
installations, the appropriate connector is to be applied only to the correct size
conductor as specified by the connector manufacturer, using only the connector
manufacturer’s recommended tooling or tooling approved for that connector.

The shelf in combination with the NE050AC48ATEZ has not been evaluated for
hot-swapping.

If the proper connector for the country of installation is not provided, obtain
appropriate connectors and follow manufacturers and all local requirements for
proper connections. All national and local rules and regulations should be
followed when making field connections.