3.9 ELECTRICAL

CONNECTIONS

WARNING !

The connections to and from the UPS must be executed by QUALIFIED PERSONNEL
ONLY.
Refer to the “Safety prescriptions - Installation
” described on page 6.

3.9.1

Common input utility

Fig. 3.9.1-1 Common input utility

Common input utility

The UPS delivered in standard version has

common input utility.
Only one input line (F1) supplies both rectifier

and bypass input terminals.

Bear in mind that when the utility fuses are

opened there is a supply failure to the rectifier
as well as to the automatic bypass and manual
bypass.

Load

X3

L1

L2

L3

N2

PE

LPS33U_

040-080_

Connecti

on comm

on_02US

Utility 1

X4

Battery

X1

L1

-1

L2

-1

L3-

1

N1

PE

-

0

+

PE

Fig. 3.9.1-2 Terminals for common input mains

X1 Utility 1 - Input utility connection

L1 = Rectifier + Bypass Phase A
L2 = Rectifier + Bypass Phase B
L3 = Rectifier + Bypass Phase C
N1 = Utility Neutral

PE = Main Ground

X3 Load - Output load connection

L1 = Load Phase L1
L2 = Load Phase L2
L3 = Load Phase L3
N2 = Load

Neutral

PE = Load Ground

LP 33 Series / 30 kVA

1 AWG (35mm

2

)

Max. rating X1, X2 and X3 terminals:

LP 33 Series / 40 kVA

4/0 AWG (95mm

2

)

Connect wire to the Terminals using appropriate tools and appropriate torque.
Torque specification for Input / Output and DC power connections on Terminals: Section 3.8.1.

NOTE !

For UPS correct operation, the input utility phase rotation must be clock-wise.
Inside the UPS, all neutrals N1
and N2 are connected together.

NOTE !

This UPS is designed to operate in a wye-configured electrical system with a solidly
grounded neutral.