Typical installation – Xylem AC5660 Series A-C 1500 Vertical In-Line Pump User Manual

Page 16

Advertising
background image

Check

Explanation/comment

Checked

Check that you have a foot valve of equal or greater

area than the pump suction piping when you use in

an open system with a suction lift.

Prevent clogging by using a strainer at the

suction inlet next to the foot valve. Make sure

that the strainer has an area three times that of

the suction pipe with a mesh hole diameter of

no less than 0.25 in. (0.64 cm).

Check that flexible piping is used on both the suction

and discharge sides of the pump when you use an

isolation base.

Check that a triple duty valve is installed in the

discharge line.

This valve serves as a check valve that protects

the pump from water hammer, and serves as an

isolation valve for servicing and for throttling.

Check that the pipeline has isolation valves around

the pump and has a drain valve in the suction pipe.

Use PTFE tape sealer or a high quality thread sealant

when you install the suction and discharge

connections to a threaded pump housing.

Typical installation

1

2

3

4

5

6

7

8

9

10

11

1.

Compression tank (located in the suction piping)

2.

Air separator

3.

System supply

4.

Circuit setter

5.

Triple duty valve

6.

Pump

7.

Suction diffuser

8.

Isolation valve

9.

Pipe from boiler, chiller, or converter

10. Cold water supply

11. Reducing valve

Check that the control and safety devices have these characteristics:

• Properly sized for their purpose
• Placed correctly in the system before putting the system into operation

Installation

14

Series A-C 1500 Installation, Operation, and Maintenance Manual