PROGRAMMING VIA DIP SWITCHES AND TRIM POTS:

To program DI2 for 3-wire control, refer to Figure 5 and perform the following:

1. Press and hold the reset button on the front of the SSW07 for 5 seconds to enter the programming mode.

Note: The reset button must remain pressed during programming.

2. When the programming mode is entered, two LED’s will illuminate (over-current and phase loss), indicating

that DI2 is programmed for fault reset.

3. To re-program for 3-wire control, switch the over-current dip-switch and return to the previous position.

Three LED’s will illuminate (over-current, phase loss, and phase sequence), indicating that DI2 is now
programmed for 3-wire control.

4. To change DI2 programming back to fault reset, switch the kick start dip-switch and return to the previous

position. Two LED’s will illuminate (over-current and phase loss), indicating that the DI2 is programmed for
fault reset.

5. Release the reset button to complete the programming.

FIGURE 7 – Trim-Pots and Dip Switch Locations