7

CONTROL WIRING TERMINALS

CONNECTIONS FOR REMOTE START/STOP

* Emergency Stop

A Safety or Emergency Stop function can be implemented
by removing the J1 jumper connecting terminals ES1
and ES2. The emergency stop device will then be wired
between ES1 and ES2. When an emergency situation
(high pressure, high temperature, …) is encountered the
device must open to disconnect control power to the
circuitry enabling the soft starter. This will then stop the
pump/motor. This control device must be sized to operate
at 2.5A at 115Vac.

CAUTION! THE EMERGENCY STOP DEVICE DOES
NOT DISCONNECT LINE POWER TO THE SOFT
STARTER.

FIGURE 4 – Control Wiring Terminals

CONTROL WIRING TERMINAL STRIP

SSW 07

Terminals

Control

Terminal

Label

Control Terminal

Description

ES1

Safety/Emergency Stop*
Connected by J1. To enable an
emergency stop function, re-
move J1 and install the control
device between ES1 and ES2

ES2

A1

1221

110Vac Control Voltage

1221

A2

1223

Neutral for Control Voltage

1223

13

1301

Connected to 1401 by J2.
J2 Enables Start and Stop
Buttons on enclosure cover.
To disable buttons on the cover,
remove J2. To add a remote
Start/Stop, connect a jumper
from 1301 to 1441 and wire the
control device between 1441
and 1403.

1401

Connection to Start and Stop
Buttons on enclosure cover.

1441

Remote Start/Stop**

1403

SP

Spares

SP

GND

Ground

GND

Control Relay

ES1

1221

1301

1401

1441

1403

SP

GND

GND

SP

1221

1223

1223

ES2