CONNECTIONS FOR REMOTE CONTROL OF THE SSW07 WHEN PURCHASED SEPARATELY

CONTROL VIA 2-WIRE START/STOP

(Remote Mode):

FIGURE 5 – Control via 2-wire Start/Stop

Control Wiring: Start/Stop switch is N.O.
(Normally Open) and is wired as shown in Figure 4.

Parameters (Optional Keypad):

1. Set P220 = 1 Always Remote

2. Set P230 = 1 Digital Inputs

3. Set P263 = 1 DI1 Enable/Disable

CONTROL VIA 3-WIRE START/STOP

(Remote Mode):

FIGURE 6 – Control via 3-wire Start/Stop

Control Wiring: “Start” and “Stop” are momentary push button switches and are connected as shown in
Figure 4. “Start” is a N.O. (Normally Open) contact and “Stop” is a N.C. (Normally Closed) contact.

Parameters (Optional Keypad):

1. Set P220 = 1 Always Remote

2. Set P230 = 1 Digital Inputs

3. Set P263 = 1 DI1 Start (three wires)

4. Set P264 = 1 DI2 Stop (three wires)