SOFT STARTER OPERATION:

The Soft Starter is now ready to operate via the 2-Wire or 3-Wire Control that was set up in the previous steps.

To start the motor, press the “Start Button” and the Soft Starter will accelerate up to speed (default acceleration
time is 20sec). When full voltage is reached the internal bypass contactors will engage and switch the motor to
the supply line.

To stop the motor, press the “Stop Button” and the Soft Starter will decelerate to the stop position (default
deceleration time is “Off” so the motor will coast to rest). For details on setting deceleration time and other trim-
pots refer to Chapter 4 in the SSW07 User’s Guide.

FAULT CODES:

Optional Keypad:
When a fault is detected, the Soft Starter is disabled and the Fault Code is displayed (example E03). To restart
the Soft Starter after a fault has occurred, the Soft Starter must be reset. Resetting the Soft Starter can be done
by disconnecting and reapplying AC power (power-off reset), by pressing the “O/RESET” key (manual reset),
automatic reset, or via digital inputs. For details on Reset and a full list and description of Fault Codes, please
read Chapter 6 in the SSW07 User’s Guide.

Trim-pots and DIP switches:
When a fault is detected, the Soft Starter is disabled and the Fault Code is displayed by flashing LED’s. To restart
the Soft Starter after a fault has occurred, the Soft Starter must be reset. Resetting the Soft Starter can be done
by disconnecting and reapplying AC power (power-on reset), by pressing the “RESET” button on the front panel
(manual reset), automatic reset, or via digital inputs. For details on Reset and a full list and description of Fault
Codes please read Chapter 6 in the SSW07 User’s Guide.