Xylem IM253 R0 AquaStart Combination Soft Starters User Manual

Page 11

Advertising
background image

11

PARAMETERS EXAMPLE (Optional Keypad) (P219 = 1):

Soft Starter Data (Example):

Enclosure Model:

AST40150

SSW-07 Model:

SSW07XY0024T5SZ

Motor Data (Example):

Power:

15 HP

Rated Speed:

3450 RPM

Motor FLA Current:

21A

Service Factor Current:

24A

Rated Voltage:

460 V

Service Factor:

1.15

The following is a typical list of parameter changes needed using the Motor/Soft Starter data shown above.

P000=5 Parameter Access (5 = Password)
P219=1 Parameterization via keypad/ (trim pots and DIP switches) (1 = keypad)
P202=0 Type of Control (0 = Voltage Ramp)
P101=50 Initial Selected Voltage (50%)
P102=20 Voltage Ramp Time (20 seconds)
P400=460 Motor Rated Voltage (460 volts)
P401=87.5% Motor Rated Current (21 amps)
P406=1.15 Motor Service Factor (1.15)
P640=6 Thermal Motor Protection Class (Class 30)

Local/Remote parameters allow the soft starter to be set up to operate from Keypad, Remote Terminal, or a
programmed combination of keypad and terminal inputs.

P220 – Local/Remote Selection
P229 – Local Status Command
P230 – Remote Status Command

Read Only Parameters (P001 – P081) can be used for monitoring and troubleshooting. For a full list and
description please read the SSW07 Programming Manual. By monitoring certain read only parameters, the
status of inputs, outputs, and soft starter operational values can be determined without the use of any other
test equipment.

P003 - Motor Current
P006 - Soft Starter Status
P007 - Output Voltage
P012 - Digital Input Status
P013 - (Relay Output Status) – used to monitor relay outputs.