Safety instructions – Xylem IM170 G&L SERIES MODEL SVI User Manual

Page 5

Advertising
background image

5

SAFETY INSTRUCTIONS

TO AVOID SERIOUS OR FATAL PERSONAL INJURY

OR MAJOR PROPERTY DAMAGE, READ AND

FOLLOW ALL SAFETY INSTRUCTIONS IN MANUAL

AND ON PUMP.
THIS MANUAL IS INTENDED TO ASSIST IN THE

INSTALLATION AND OPERATION OF THIS UNIT

AND MUST BE KEPT WITH THE PUMP.

This is a SAFETY ALERT SYMBOL.

When you see this symbol on the pump

or in the manual, look for one of the

following signal words and be alert

to the potential for personal injury or

property damage.
Warns of hazards that WILL cause

serious personal injury, death or major

property damage.
Warns of hazards that CAN cause

serious personal injury, death or major

property damage.
Warns of hazards that CAN cause per-

sonal injury or property damage.

NOTICE: INDICATES SPECIAL INSTRUCTIONS

WHICH ARE VERY IMPORTANT AND

MUST BE FOLLOWED.

THOROUGHLY REVIEW ALL INSTRUCTIONS

AND WARNINGS PRIOR TO PERFORMING ANY

WORK ON THIS PUMP.
MAINTAIN ALL SAFETY DECALS.

UNIT NOT DESIGNED FOR USE

WITH HAZARDOUS LIQUIDS OR

FLAMMABLE GASES. THESE

FLUIDS MAY BE PRESENT IN

CONTAINMENT AREAS.

• Provide adequate space and ventilation around unit for

service and for motor cooling.

• Protect the pump and piping from freezing tempera-

tures.

• The unit MUST be securely affixed to a level metal

base foundation, adequate to absorb vibration and pro-

vide permanent, rigid support for the pump and motor

assembly. See the “ENGINEERING DATA” section of

this manual for specific model weights and pump base

dimensions.

NOTICE: DO NOT DRAW PIPING INTO PLACE BY

FORCING THE PUMP DISCHARGE

CONNECTIONS.

• Discharge piping should be no smaller than the

respective pump opening and should be kept as short

as possible, avoiding unnecessary fittings to minimize

friction losses.

DANGER

WARNING

CAUTION

WARNING

Hazardous fluids

can cause fire,

burns or death.

NOTICE: PIPING MUST BE INDEPENDENTLY SUP-

PORTED AND NOT PLACE ANY PIPING

LOADS ON THE PUMP.

• Insure that the size and minimum liquid submergence,

over the suction inlet, is sufficient to prevent air from

entering through a suction vortex. See typical suction

piping Figures 1 and .

• Install a discharge check valve, suitable to handle the

flow and liquids, to prevent backflow.

• Install an appropriately sized gate valve, AFTER the

discharge valve, to regulate the pump capacity, for

pump inspection and for maintenance.

• When a pipe increaser is required, install between the

check valve and the pump discharge.

• When the pump is purchased less motor, the pump will

be supplied with a motor assembly shim positioned

between the motor adapter and the coupling.

• To assemble the motor to the pump remove the plastic

shipping straps, the  stainless steel coupling guard

halves, and the expanded polyurethane.

• Insure that the motor assembly shim is properly posi-

tioned between the coupling and the motor adapter. If

the motor assembly shim is not available, a 0.03"

(5 mm) shim may be used to locate the pump shaft

assembly and to set the correct height.

• For motor frame sizes 13TC and larger, attach the

motor adapter flange to the motor using  hex cap

screws. Torque to values shown in the

“ENGINEERING DATA” section of this manual.

• Loosen the  coupling socket head screws enough to

provide an adequate opening in the coupling to receive

the motor shaft.

• With an adequately sized crane, carefully lower the

motor assembly onto the pump motor adapter and

into the coupling. Secure the  motor hex cap screws,

torquing to the value provided in the

“ENGINEERING DATA” section of this manual.

• Torque the  coupling socket head screws to the value

provided in “ENGINEERING DATA” section of this

manual.

• Remove the motor assembly shim and retain for future

use.

• Install the  coupling guard halves.

Figure 1

Figure 2

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

H = Min. Submergence in feet

8D

min.

4D

min.

=GPM x 0.321

Area

GPM x 0.4085

D2

min.

3D

2

V = Velocity in feet per second

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 V

H

H min.

3D

D

3D

Advertising