Guideline

Explanation/comment

When possible, locate the pump below the fluid

level.

This facilitates priming, ensures a steady flow of liquid, and

provides a positive suction head on the pump.

Foundation requirements

Requirements

• The foundation must be able to absorb any type of vibration and form a permanent,

rigid support for the unit.

• The foundation must weigh at least 2-1/2 times the weight of the pump unit.
• Provide a flat, substantial concrete foundation in order to prevent strain and distortion

when you tighten the foundation bolts.

• Sleeve-type and J-type foundation bolts are most commonly used. Both designs allow

movement for the final bolt adjustment.

• Tie the concrete pad in with the finished floor.
• Use foundation bolts and larger pipe sleeves to give room for final bolt location.

Diagram

2

3

1

4

1.

Foundation bolt

2.

Pipe sleeve

3.

Washer

4.

Built-up concrete foundation

Piping checklist

WARNING:

• The heating of water and other fluids causes volumetric expansion. The associated

forces can cause the failure of system components and the release of high-
temperature fluids. In order to prevent this, install properly sized and located
compression tanks and pressure-relief valves. Failure to follow these instructions can
result in serious personal injury or death, or property damage.

• Avoid serious personal injury and property damage. Make sure that the flange bolts

are adequately torqued.

• Never force piping to make a connection with a pump.

Check

Explanation/comment

Checked

Check that a section of straight pipe, with a length that

is five times its diameter, is installed between the

suction side of the pump and the first elbow, or that a

B&G Suction Diffuser is installed.

This reduces suction turbulence by

straightening the flow of liquid before it enters

the pump.

Installation

14

Series e-1510 Installation, Operation, and Maintenance Manual