Typical installation, Special installation, Install the pump, driver, and coupling – Xylem P2001406B Series e-1510 Centrifugal Pumps User Manual

Page 18: Typical installation special installation

Advertising
background image

Typical installation

4

5

6

7

8

10

9

1

2

3

11

12

13

14

1.

Expansion tank

2.

B&G Rolairtrol

®

air separator

3.

Supply to system

4.

TPV Tank Purge Valve

5.

B&G Triple Duty

®

valve

6.

B&G Series e-1510 Pump

7.

B&G Suction Diffuser

8.

Isolation valve

9.

Pipe from boiler, chiller, or converter

10. Cold water supply

11. B&G Pressure Reducing Valve

12. B&G Model 107A — High capacity vent

13. B&G #7 or #87 Air Vent

14. Drain valve

Special installation

Installation with suction diffuser and triple-duty valve

Do not install and operate triple-duty valves and suction diffusers in closed systems unless
the system is designed with these safety and control devices:

• Pressure relief valves
• Compression tanks
• Pressure controlling equipment
• Temperature controlling equipment
• Flow controlling equipment

Check that the control and safety devices have these characteristics:

• Properly sized for their purpose
• Placed correctly in the system before putting the system into operation

Installation with isolation base

When using an isolation base, flexible piping should be used on both suction and
discharge sides to reduce the strain on the flanges.

Install the pump, driver, and coupling

Perform these steps only if the unit was not installed at the factory.

Installation

16

Series e-1510 Installation, Operation, and Maintenance Manual

Advertising