All other functions are disabled in this mode, L. other “tool” menu options, A) click on “echo profile” button – Xylem WL900 RADAR LEVEL TRANSMITTERS User Manual

Page 10: B) click on “clear window out, C) click on “freeze/update/window out

Advertising
background image

Global Water

800-876-1172

globalw.com

- 10 -

i. “AutoScan” button (only for network): Collects data for all sensors

connected in the network. Scanning time for one sensor is 30 seconds.

Other functions are disabled in Auto Scan mode.

j. “SensorStatusMonitoring” function displays status of selected sensor.

1. Push the “Update_all” command button to display status for all

sensors in network.

2. Traffic icon green/red light indicates communication status.

3. All other functions are disabled in this mode.

k. “Select COM Port”: Used to select Communication Port on PC. Selected

port can be saved to be used as a default when application is run again.

l. Other “Tool” menu options:

1. “Low Dielectric Material On”: For low dielectric constant materials

such as oils.

2. “Select PIPE”: For microwave propagation in metal pipes, after that

click on “Select Pipe Diameter” in “Tools” menu to choose proper

diameter of metal pipe.

3. “Window Out”: In case of unwanted reflections this procedure can

be used.

Make sure that the probe is in fast response mode (“Damping

OFF”).

Before using the Window Out procedure programmable calibration

on full and empty tank is recommended. For the first time users of

this procedure, contact with technical support group is

recommended. To use the procedure follow this:

a) Click on “Echo Profile” button

b) Click on “Clear Window Out”,

c) Click on “Freeze/Update/Window Out”,

d) Using mouse, click on a point before unwanted echo and

then on “WindowOutMin”,

e) Using mouse, click on a point after the unwanted echo and

then on “WindowOutMax”,

f) Close the Echo Profile and wait in the Main program for a

message “WindowOut” calibration done,

g) To activate the “Window Out” procedure, go to the “Tools”

menu, click on “Window Out”, and wait for the conformation.

Advertising