X. Calibration

a. FULL: Calibrate 20 mA or 4mA. Set near target. (See Figure 7, page 18.)

1. Calibration mode LED color is Green. (For Radar, Low Dielectric

Materials has to be off. See step C.)

2. Push button and hold until LED turns Yellow (20 mA) or push button

and hold until LED turns Red (4 mA)

3. Release button, observe LED flashes to acknowledge the

calibration.

b. EMPTY: Calibrate 4 mA or 20 mA. Set Far Target. (See Figure 7, page

18.)

1. Calibration mode LED color is Green. (For Radar, Low Dielectric

Materials has to be off. See step C.)

2. Push button and hold until LED turns Red (4 mA) or push button

and hold until LED turns Yellow (20 mA)

3. Release button, observe LED flashes to acknowledge the

calibration.

c. Turn the Low Dielectric Materials operation mode ON and OFF:

(This mode is recommended for materials with dielectric constant lower

than 4, and to eliminate multiple reflections in the tank.)

1. To turn the Low Dielectric Materials ON, push the calibration button

and hold until the LED light flashes yellow, then red, and then turns

off. Release the button. The blinking green LED light indicates that

the Low Dielectric Materials mode is ON

2. To turn the Low Dielectric Materials OFF, push the calibration

button and hold until the LED light flashes yellow, then red, and

then turns off. Release the button. The constant green LED light

indicates that the Low Dielectric Materials mode is OFF.

3. The low dielectric materials operation can also be turned ON or

OFF with the Radar Level Transmitter software during PC

communications, which is recommended.