“pipe mode” on/off (for microwave probe only), “select pipe diameter” (for microwave probe only), “damping off”: fast response mode of the probe – Xylem WL900 RADAR LEVEL TRANSMITTERS User Manual

Page 9: “damping on”: select damping time

Advertising
background image

Global Water

800-876-1172

globalw.com

- 9 -

9. “Temperature Scale”: (Not applicable for microwave probe.)

10. “Low Dielectric Material”: (choose for low dielectric constant

materials, for microwave probes only)

11. “Pipe Mode” On/Off (for microwave probe only)

12. “Select Pipe Diameter” (for microwave probe only)

13. “Damping OFF”: Fast response mode of the probe

14. “Damping ON”: Select damping time

d. “ShowCalibData” (Show Calibration Data): Screen displays all calibration

parameters.

e. The fix point Calibration buttons (the same as using the probe calibration

Push Button) are in the top left corner of the screen. “F.T Calib.” is for Full

Tank Calibration and “E.T. Calib.” is for Empty Tank Calibration. In this

calibration a target has to be used to simulate full or empty tank fix point

calibration.

f. “Diagnostic” button: Displays all information on probe “errors”. Sensor error

is indicated by an unhappy face icon at the bottom of the screen.

g. “Echo Chart” button: Displays information on stability of the echoes.

Calculated echo peak count basis on peak width voltage is used as an

echo correction offset.

h. “Echo Profile” button: Displays profiles of your probe.

NOTE - when using this feature the probe is not in the measurement

mode. To return to measurement mode, exit the echo profile (select x).

Wait until you get the Data Link OK (green light on the Probe Status LED).

1. On the “echo profile” you will see a marker where the software

picked up an echo and the distance to the target.

2. To change target for different measurement, exit profile screen, wait

for updated data, and go to echo profile. The marker will pick up the

new target. Freeze screen and select any point on the graph by

clicking mouse to display the distance to selected target.

3. 'Save to file' command saves the profile to PROBE_PROFILE file in

C:\Program Files\um_probe\ folder.