Franklin Fueling Systems Colibri CL6 Setup and Operators Guide User Manual
Page 30

30
Starting Autocal
When Autocal starts, it will need a reference volume as
the starting point for the calibration. The default reference
volume will be what the tank gauge is reading at the
time that Autocal is started. This reading needs to be as
accurate as possible
and not higher than the initial
volume read by the ATG, in order to produce a quality
chart. The Diameter, Length, and Correction Points are
what contribute to the default volume’s accuracy. The
diameter of the tank should be listed on the tank chart, but,
if it’s not, then it can be easily measured.
To begin the Autocal process;
1. Select a tank from the Inventory Summary Screen.
2. After selecting the tank, press the (MENU) key in
the upper right hand corner.
3. Next, select Control/Tanks/Autocalibration.
4. Select the tank and this message should
appear “Are you sure you want to perform the
autocalibration on this tank?” Select OK.