Figure g-1 – exp analog input module connections – Franklin Fueling Systems T5 Series Fuel Management System Installation Guide User Manual
Page 22

22
4-20mA EXP
Analog Input
Module
RUN
ERR
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
- (BLK)
+ (RED)
LSU500E
Hazardous Location
Non-Hazardous
Location
Explosion-Proof Conduit
- (BLK)
+ (RED)
4-20mA
Sensor
Figure G-1 – EXP Analog Input Module Connections
Appendix G: 4-20mA EXP Analog Input Module (420EXP)
The 420EXP has 8 identical channels for loop powered non-IS
sensors with a 4-20 mA interface. The T5 series can support up
to 24 inputs (3 modules total including 420IB models with 8 inputs
each) depending on available space in your console. The 420EXP
will most likely be used with explosion proof version of the line leak
pressure transducers at the sites where IS wiring is not available.
It can also be used with other 4-20 mA sensors located in non-
hazardous area.
Note: Components located in the hazardous area must be an
explosion proof version and wiring must be enclosed in explosion proof conduits.
EXP Analog Input Module Specifications
Number of Channels: 8
Loop Power
24 Volts
Internal Resistance
350 ohms