Scm alarms – Franklin Fueling Systems TS 550 evo Fuel Management System Operators Guide User Manual
Page 36

32
Displayed Alarm /
Warning
Device
Description
Recommended Actions
SCM Alarms
Containment Not
Learned
SCM
The learning process has not been
completed.
Refer to Secondary Containment Monitoring Installation and User’s
Guide 000-0528 for more information.
Containment Program
Error Detected
SCM
An error has been detected in the
containment programming.
Containment Program
Error Warning
SCM
An error has been detected in the
containment programming
Containment Pump
Request Ignored
Engineering The containment called for the
STP to turn on but has not seen an
increase in vacuum level.
Failed to Hold Vacuum
SCM
The rate of vacuum decay faster
than the learned rate.
Failed to Reach Target
Vacuum
SCM
6”hg could not be reached in the
learned time.
Low Vacuum
SCM
The vacuum level has dropped
below 1”hg.
Low Vacuum And Pump
Request Ignored
Engineering Low vacuum level due to Pump
Request Ignored.
Not Configured
SCM
Containment programming has not
been completed
Unstable Vacuum
SCM
Vacuum level is fluctuating at a rate
that is FFSsistent with the learned
parameters.
Vacuum Sensor Failed
SCM
The 4-20mA vacuum transducer
has failed and is no longer
detected
Vacuum Too High
SCM
The vacuum level has reached
above 10”hg