AC Input Module (ACI)

The ACI is a non-intrinsically safe module that has 12 

identical optically isolated AC input channels that can be 

used for dispenser hook isolation, vapor processor input, 

or as generic AC inputs.  The TS-550 evo consoles can 

handle a total of 36 AC inputs or up to three AC Input 

Modules in one system.

AC Input Module Specifications

Number of Channels:

12 optically isolated

Input Voltage Rating:

110 – 240 VAC

Input Current:

7 mA RMS

Dispenser Hook Signals

The TS-550 evo system requires that the dispenser hook 

signal from every dispenser on site be wired into the 

console’s AC Input Module. When making the connection 

for the hook signals to the AC Input Module, refer to the 

following diagram and use these guidelines:
 • If there are two hooks per dispenser: wire the two hooks 

from Dispenser 1 to AC input channels 1 & 2, the hooks 

from Dispenser 2 to AC channels 3 & 4, etc..

 • If there are three hooks per dispenser, then wire the 

three hooks of Dispenser 1 to the AC input channels 1, 

2, 3 and so forth.

AC Input

Module

RUN

ERR

Chan

3

Chan

2

Chan

1

Chan

6

Chan

5

Chan

4

Chan

12

Chan

11

Chan

10

Chan

9

Chan

8

Chan

7

Incoming

Dispenser

Hook Signal

Line
Neutral

Line

Neutral

Line

Neutral

Vapor Processor

(optional)

Generic Device

(optional)

Figure 12: Dispenser Hook Signal

4-20mA EXP Analog Input Module (420EXP)

The 420EXP has 8 identical channels for loop powered 

non-IS sensors with a 4-20 mA interface. The TS-550 

evo series can support up to 24 inputs (3 modules total 

including 420IB models with 8 inputs each) depending on 

available space in your console. The 420EXP will most 

likely be used with explosion proof version of the line leak 

pressure transducers at the sites where IS wiring is not 

available. It can also be used with other 4-20 mA sensors 

located in non-hazardous area.

EXP Analog Input Module Specifications

Number of Channels:

8

Loop Power

24 Volts

Internal Resistance

350 ohms

Note: Components located in the hazardous area must be 

an explosion proof version and wiring must be enclosed in 

explosion proof conduits. 

4-20mA EXP

Analog Input

Module

RUN

ERR

+

+

+

+

+

+

+

+

- (BLK)

+ (RED)

LSU500E

Hazardous

Location

Non-Hazardous

Location

Explosion-Proof Conduit

- (BLK)

+ (RED)

4-20mA

Sensor

Figure 13: EXP Analog Input Module Connections