Franklin Fueling Systems TS-DIM User Manual
Page 12

12
Gilbarco
G-SITE
Controller
C2 Style
TS-DIM/GS
RJ45 to DB9 Adapter
(P/N 601-1002)
RJ45 to DB25 Adapter
(P/N 601-1001)
Note: If the 600-0205 cable is not long enough for your installation, a standard CAT5
cable may be substituted.
TS-DIM/GS to Gilbarco C2 G-SITE
Gilbarco
G-SITE
Controller
486 Style
or Passport
TS-DIM/GS
RJ45 to DB9 Adapter
(P/N 600-1005)
TS-DIM/GS G-SITE Adapter Cable
(P/N 600-0205)
Note: G-SITE systems must support EMC with BIR interface. Minimum software
levels must exist on the G-SITE for proper operation.
TS-DIM/GS to Gilbarco 486 G-SITE or Passport
TS-DIM/GS G-SITE Adapter Cable
(P/N 600-0205)
Note: G-SITE systems must support EMC with BIR interface. Minimum software
levels must exist on the G-SITE for proper operation.
Figure 9
Port 5
Dongle Cable
Gilbarco Part # M09747B010
PassPort 8.02
TS-DIM/GS
Dispenser Security Hub
Part # 600-0205
601-1002
601-1005
Gilbarco Passport
1. Using TSP-GSDCBL connect the 600-1002 adaptor to the port on the TS-DIM/GS.
2. Connect the 600-1005 to the end of the dongle cable Gilbarco Part # M09747B010
3. Connect the dongle cable to Port on Dispenser Security Hub (port 5) if available
4. Setup EMS DIM 1 to G site and RS232/Duplex
5. Be sure Port on Security hub is set to EMC and Baud 1200, 7, E, 1
6. Query Dispensers.
Figure 10