Disable Transmission of Unsolicited Alarms

“509 None (xxxx)”; xxxx= “active” or blank; default is “active.”

Setting this option to “active” disables the transmission of all unsolicited

alarm messages. USER SECURITY CODE is required to set this option.

Transmit IPC-XXX Type Unsolicited Alarms

“IPC-XXX (xxxx)”; xxxx= “active” or blank; default is blank

Setting this option to “active” causes unsolicited alarm messages of type

IPC-XXX to be transmitted whenever the status of the CFR changes. These
are ASCII type messages which are sent on the RS-232 port. The USER
SECURITY CODE is required to activate this option.

The following is a list of the unsolicited alarm messages.

UPS000 - power up
UPS001 - input out of tolerance
UPS002 - input blackout
UPS003 - inverter on
UPS004 - line mode
UPS005 - low battery warning
UPS006 - low battery shutdown
UPS007 - overload
UPS008 - load OK
UPS009 - temperature high
UPS010 - temperature OK
UPS011 - service required
UPS012 - UPS malfunction
UPS013 - self-test (Inv. on)
UPS014 - self-test passed (line mode)
UPS015 - self-test failed

Delay Transmission of Inverter On Unsolicited Alarms

“Inverter on Alarm Delay (xxxxx)”; xxxxx= “off” or “m=min”, where m

specifies 1 to 5 minutes; default setting is “off”.

Transmission of the “inverter on unsolicited message,”

(i.e.,UPS003 -

inverter on), can be delayed for 1 to 5 minutes to prevent short interruptions in
the input AC line from being displayed. Setting this option to “off” causes all
AC line interruptions to be displayed. USER SECURITY CODE is required to
change this option.

511

509

5. RS-232 TERMINAL COMMUNICATION

5.9 User Parameters,

continued