Specifications 7.1 specifications – Alpha Technologies CFR 600, CFR 600XT, CFR 1000 User Manual

Page 66

Advertising
background image

60

7. SPECIFICATIONS

7.1 Specifications,

continued

Common Specifications

600, [1000 ]

Input Frequency

60 Hz or 50 Hz (± 3% Hz)

Input Voltage Variation

- 25% to + 10%

Output Frequency

± 0.1 Hz

Output Regulation

± 1% (from 10 - 100% load)

Total Harmonic Distortion

< 5%

Output Waveform

Sine

Step Load Response

< 10% @ 100% load

Noise Attenuation

Common Mode

-120dB (100K - 1 MHz)

Normal Mode

-60dB (100K - 1 MHz)

Low Voltage Trigger

80% nominal voltage (adjustable)

High Voltage Trigger

110% nominal voltage (adjustable)

Batteries

Valve regulated, maintenance-free

Battery Voltage

24 VDC

Batt. Low Volt. Cutout

19.5 VDC (>25% load), [21 VDC (<25% load)]

Charger

Linear (3.5 A max.)

Charger Voltage

27.6 VDC at 25

0

C (adjustable)

Operating Temp

32

0

-104

0

F / 0

0

- 40

0

C

Heat Output

260 BTU, [404 BTU]

Indicators

Line Present, Line Failure,
Low Battery Shutdown,
Low Battery Warning (LED / audible alarm),
Test, Service and Output Load

Controls

Manual Start / Test, Alarm OFF

Connectors

AC Input, AC Output, External Alarm;
Intelligent Interface Device and
External Battery

Output Alarms

Rear panel RJ-45 connector (Form C
contact closures rated 1A, 30 V) for
Line Present / Line Failure, and
Battery OK / Low Battery Warning

Specifications subject to change without notice.

Advertising