5. RS-232 TERMINAL COMMUNICATION

5.11 Parameter Dump Command (Function 0)

Parameter Dump Command (Function 0)

Function ‘0’ displays all UPS parameters in the following format:

#####,###.#,#####,#####,##.##,###.#,#####,###.#,#####,###.#,#####,#####,##.##,
###.#,###.#,###.#,xxxxx,#####,#####,#####,#,##,##,##,##,##,##,##,##,

###############,############ <CR> <LF>

Where ‘#’ indicates a digit or a blank character and ‘x’ represents a

letter. The string is terminated by a Carriage Return and a Line Feed.
Parameters are separated by a comma (‘,’). Above is the exact format for
the SID option; IID option has slightly different format (less blank charac-
ters). This command lists the CFR parameters in the following order:

1. Input Voltage

17. Charger Status

2. Input Current

18. Battery Temperature

3. Input VA

19. Efficiency

4. Input Watts

20. Capacity

5. Input Power Factor

21. Run Time Remaining

6. Input Frequency

22. Mode Data

7. Output Voltage #1

23. Input Alarms #1

8. Output Current #1

24. Input Alarms #2

9. Output Voltage #2

25. Battery Alarms

10. Output Current #2

26. Output Alarms

11. Output Watts

27. Environmental Alarms

12. Output VA

28. Inverter Alarms

13. Output Power Factor

29. System Alarms

14. Output Frequency

30. IID/Micro Board Serial #

15. Battery Voltage

31. Unit model - config. version

16. Battery Current

Example:
114, 1.22, 133, 38, 0.29, 59.9, 127, 0.31, 222, 0.49, 95, 0, 0.00,
59.9, 55.2, 2.8,ON , 24, 0, 0, 0,00,00,00,00,00,00,00,00,
88430A000000CA,001060001000<CR><LF>

0

42

In the above example, 114 represents the Input Voltage, 1.22 repre-

sents the Input Current, 133 represents the Input VA, etc.