59

7.1 Specifications

Output Power (VA)
Active Power (WATTS)
Input Voltages @ 50 Hz (VAC)
Input Current Max. (A)
Input Voltages @ 60 Hz (VAC)
Input Current Max. (A)

Output Voltages @ 50 Hz (VAC)
Output Current Max. (A)
Output Voltages @ 60 Hz (VAC)
Output Current Max. (A)

Efficiency @ Full Load (%)
Efficiency @ .25 Load (%)
Max Charger Current (A)
Batt Run Time* - internal (min)
Battery Recharge Time (hrs)

Audible Noise @ 1M (dBA)

CFR

600
600
400
230

2.5

120

4.8

230

2.6

120

5.0

84
63

3.5

8

2.0

<40

Dimensions
CFR 600

8.5"W x 10"H x 20.5"D (205mm x 140mm x 194mm)

CFR 1000

8.5"W x 10"H x 20.5"D (216mm x 254mm x 521mm)

EBP 24A

8.5"W x 5.5"H x 15.5"D (216mm x 140mm x 194mm)

EBP 24C

8.5"W x 9.75"H x 24"D (216mm x 248mm x 610mm)

EBP 24E

8.5"W x 21.5"H x 31"D (216mm x 546mm x 787mm)

Weights

60 Hz Units

50 Hz Units

CFR 600

52 lbs. (39.5 kg)

56 lbs. (26 kg)

CFR 600XT

69.5 lbs. (24 kg)

74 lbs. (33.6 kg)

CFR 1000

93.5 lbs. (42.4 kg)

94 lbs. (42.5 kg)

EBP 24A

35 lbs. (16 kg)

35 lbs. (16 kg)

EBP 24C

125 lbs. (57 kg)

125 lbs. (57 kg)

EBP 24E

314 lbs. (142 kg)

314 lbs. (142 kg)

The EBP 24A is an external 24 volt battery pack, pre-wired, with two, 17

Ah maintenance free batteries.

CFR

1000
1000

750
230

4.3

120

8.3

230

4.3

120

8.3

92
90

3.5

12

5.0

<40

CFR

600XT

600
400
230

2.5

120

4.8

230

2.6

120

5.0

84
63

3.5

28

5.0

<40

* Battery run times are calculated

at typical load (80%)

Specifications subject to change without notice.

Note: Specifications are based upon use with computer-type loads with a crest factor of 3:1 max., and a
typical power factor of 0.75 for CFR 1000 and 0.67 for CFR 600.

7. SPECIFICATIONS