Alpha Technologies BPT Series Bypass Transformer User Manual

Page 11

Advertising
background image

3.2 Bypass Switch Installation

CAUTION: The installation and testing of the Bypass Switch must be performed only by

qualified personnel familiar with installing electrical equipment. This must be done in

accordance with the rules and regulations of local and national electrical codes.

The installation of a bypass circuit breaker is required. To select the proper size circuit breaker

refer to Table 2.

Procedure:
1. Select an appropriate location for the Bypass Switch (and Bypass Transformer if required).

The Bypass Switch can be mounted to a wall close to the UPS. The Bypass Transformer

can be either wall or floor mounted.

2. Connect the BPS (and BPT if required) to the UPS and utility following the schematic wiring

diagram applicapable to your configuration as specified in Table 1. Refer also to Table 2 to

select the proper size circuit breaker and wire gauge.

3. Before placing the BPS-UPS into service, perform the test procedure outlined in Section

4.1 on page 9 of this manual. It is important that both sources of power are “in phase” to

provide trouble free Bypass Switch operation.

Table 2 : Bypass Circuit Breaker Current Rating

UPS Model

Systems Without

Bypass Transformer

Systems With Bypass Transformer

Max UPS

Output

Current (Amps)

Bypass

CB Rating

(Amps)

Wire Size

(AWG)

Input Rating

of BPT @

208 Vac

(Amps)

Bypass

CB

Rating

(Amps)

Wire Size for

208 Vac or

240 Vac Loads

(AWG)

Wire size for

120 Vac Load

(AWG)

CFR 1500

(or smaller)

12.5

15

#14

8

15

#14

#14

CFR 2000

17

20

#12

11

15

#14

#12

CFR 2500

21

30

#10

13

15

#14

#10

CFR 3000

25

40

#8

16

20

#12

#8

CFR 4000

33

50

#6

21

30

#10

#6

CFR 5000

41

60

#6

27

40

#8

#6

CFR 7.5K

36

50

#6

36

50

#6

N/A

CFR 10K

48

60

#6

48

60

#6

N/A

CFR 15K

72

90

#3

72

90

#3

N/A

1600 EP

18KVA

75

90

#3

75

90

#3

N/A

Notes:

Current ratings for CFR 5000 and smaller units are based on 120V rated output. This is because the rated output of L1 is

capable of supplying the full 120V current. Current ratings for CFR 7.5K - 15K are based on the maximum current rating for L1

and L2 combined (refer to the appropriate Operator’s Manual for further details).

Wire sizes are based on three current carrying copper conductors rated at 75 deg. C and are guidelines only. Always follow

your local electrical code.

Installation

Doc# 020-133-B0 Rev. 01 / 07

7