Alpha Technologies BPT Series Bypass Transformer User Manual

Page 8

Advertising
background image

2.4 Bypass Switch Selection Guide)

Table 1 – Bypass Model Selection Guide

Configuration

CFR 3000 or Smaller

CFR 4000 or CFR 5000

1600 EP

18 KVA

Input

Output

MBB

BBM

MBB

BBM

MBB

120V

120V

BPS 2M3P

Figure 6.1

BPS 2B3P

Figure 6.1

BPS 2M3P

Figure 6.1

BPS 2B3P

Figure 6.1

Not

Applicable

120V

120V

208V

BPS 2M3P

Figure 6.2

BPS 2B3P

Figure 6.2

BPS 2M3P

Figure 6.2

BPS 2B3P

Figure 6.2

120V

120V

240V

BPS 2M3P

Figure 6.3

BPS 2B3P

Figure 6.3

BPS 2M3P

Figure 6.3

BPS 2B3P

Figure 6.3

208V

120V

BPS 2M3P BPT

3000-S or BPT

3000

Figure 6.5

BPS 2B3P

Figure 6.4

BPS 2M3P BPT

5000-S or BPT

5000

Figure 6.5

BPS 2B3P

Figure 6.4

208V

120V

208V

BPS 2M3P BPT

3000

Figure 6.7

BPS 2B3P

Figure 6.6

BPS 2M3P BPT

5000

Figure 6.7

BPS 2B3P

Figure 6.6

208V

120V

240V

BPS 2M3P BPT

3000-S or BPT

3000

Figure 6.8

BPS 2B3P BPT

3000-S or BPT

3000

Figure 6.8

BPS 2M3P BPT

5000-S or BPT

5000

Figure 6.8

BPS 2B3P BPT

5000-S or BPT

5000

Figure 6.8

BPS 3M3P

SC25BK

Figure 6.8

240V

120V

BPS 2M3P

Figure 6.9

BPS 2B3P

Figure 6.9

BPS 2M3P

Figure 6.9

BPS 2B3P

Figure 6.9

Not

Applicable

240V

120V

208V

BPS 2M3P BPT

3000

Figure 6.7

BPS 2B3P BPT

3000

Figure 6.7

BPS 2M3P BPT

5000

Figure 6.7

BPS 2B3P BPT

5000

Figure 6.7

240V

120V

240V

BPS 2M3P

Figure 6.11

BPS 2B3P

Figure 6.11

BPS 2M3P

Figure 6.11

BPS 2B3P

Figure 6.11

BPS 3M3P

Figure 6.11

230V

230V

50Hz

BPS 2M3P

Figure 6.12

BPS 2B3P

Figure 6.12

BPS 1M3P

Figure 6.12

BPS 2B3P

Figure 6.12

Not

Applicable

Notes:

The bypass system consists of the bypass switch (BPS) and bypass transformer if required (BPT).

References to Figures indicate applicable connection diagram.

N/A indicates the configuration is not available for this model of UPS.

MBB = Make Before Break Switch (Provides uninterrupted transfer).

BBM = Break Before Make Switch (Output will be interrupted for at least 30 milliseconds).

Explanation of Bypass Switch ordering code:

BPS xyzz

x = 1 :

40 Amp contact rating

x = 2 :

80 Amp contact rating

x = 3 :

125 Amps contact rating

y = M :

Make-Before-Break contacts

y = B :

Break-Before-Make contacts

zz = 3P : 3 pole switch

The Alpha BPS Series

Doc# 020-133-B0 Rev. 01 / 07

4

Advertising
This manual is related to the following products: