3.3 Circuit Breaker Rating and Wire Guage

Systems with a Bypass Isolation Transformer Installed:
Install a Bypass Circuit Breaker with the current rating specified in Table 2. Use the wire

gauge, as specified, for all connections to the Bypass Switch, especially if there is 208V or

240V supplied to the load.

CAUTION: For UPS output configurations which supply both 120V and 208 / 240V

loads, care must be taken not to overload either of the output windings of the Bypass

Transformer. The maximum current of each output winding is limited to the current rating

at 208V (i.e., the maximum current rating for L1 or L2 is the VA rating of the transformer

divided by 208). Although CFR models up to 5000 VA are capable of supplying the

full rated power at 120V from L1, systems with a bypass transformer must have the

120V loads split between L1 and L2. For CFR models 7.5K and greater the Bypass

Transformer rating is the same as the UPS output rating. Refer to the CFR Operator’s

Manual for a complete description on Load Sharing.

Without Bypass Isolation Transformer Installed:
Install a Bypass Circuit Breaker with a current rating shown in Table 2. Use the wire size

specified for all connections to the Bypass Switch.

The Alpha BPS Series

Doc# 020-133-B0 Rev. 01 / 07