3. INSTALLATION

3.2.1 Terminal Block Input and Output Wiring

, continued

* CAUTION: Refer to the nameplate voltage and frequency ratings affixed to the
unit. This power supply was wired for this particular voltage configuration when
it was shipped from the factory.

**Units shipped as 60Hz, single 120V output, do not use L2.

CFR 1500, CFR1500RM Terminal Block Output

Frequency

Voltages*

L1

N

L2**

60Hz

120 / 208VAC

120VAC

Neutral

208VAC

60Hz

120 / 240VAC

120VAC

Neutral

240VAC

50Hz

230 VAC

Not used

Neutral

230 VAC

CFR 1500, CFR 1500RM Terminal Block

Wire Guage and Tourque

MODEL

TERMINAL BLOCKS

TIGHTENING TORQUE

AWG

mm

2

Inch

Newton

Pounds

Meters

CFR 1500
CFR 1500 RM

14

2.0

35

4.0

Table 3.2.1

Table 3.2.3

WARNING: Overcurrent protection for the AC output circuit must be provided at
the time of installation.

CFR 1500, CFR 1500RM Terminal Block Input

Frequency

Voltage*

L

N

60Hz

120 VAC

120 VAC

Neutral

60Hz

208VAC

1

2

60Hz

240VAC

1

2

50Hz

230 VAC

230 VAC

N

e

u

t

r

a

l

Table 3.2.2

52

52

520

521

5.10 External Modem Parameters

External Modem setup:

This menu displays all the current external modem values. Refer

to each individual menu item for a detailed description.

Enable Automatic Alarms:

Y= Yes, N= No,

(Default value is “No”)

Setting “Enable Automatic Alarm” to “Yes” causes the modem to

dial out and report a problem whenever the specified power events (see
menu 522) happens. When enabling this feature, ensure that the Unsolicited
alarm feature (menu 509) is disabled. Always enable this feature near the
end of the modem configuration because CFR will try to communicate to
the modem two minutes after activating this feature.

Enable Remote Access:

Y= Yes, N= No,

(Default value is “No”)

Setting “Enable Remote Access” to “Yes” causes the CFR to set

the modem to answer remote calls on the first ring. Once a connection is
established, the remote host can access all CFR menus. The connection
exists until either the host drops the connection or the “Remote Hang Up
Time” expires (refer to menu 528). Enable this feature near the end of the
modem configuration because CFR would try to communicate to the
modem two minutes after activating this feature.

5. TERMINAL COMMUNICATION