6 troubleshooting guide – Alpha Technologies CFR 1500, CFR 1500RM User Manual

Page 74

Advertising
background image

5

2. FEATURES

2.1

A Tour of the CFR

The Alpha CFR is designed to be easy to use and extremely flexible. The

CFR’s interchangeable front panel interface devices provide you with a wide range
of information management options. The rear panel accepts a variety of connectors
and receptacle plates to facilitate your most demanding communication and powering
needs.

2.2

The CFR Front Panel

The CFR front panel comes equipped with a Standard Interface Device

(SID), or an optional Intelligent Interface Device (IID), to display vital UPS operating
parameters. The front panel can be easily removed for service or battery access
by loosening the two screws located in the lower grill.

Fig.1

CFR 1500 Front Panel

Standard Interface Device

Panel Screws

68

SYMPTOM

CAUSE

REMEDY

6. MAINTENANCE

6.6

Troubleshooting Guide

Utility power outage;

or

AC power cord
unplugged;

or

AC input circuit breaker
OFF.

and

BATTERY circuit
breaker OFF.

AC line voltage too high
or low;

or

UPS is in its synchr-
onization mode.

BATTERY breaker
tripped.

or

Internal charger fuse
open.

or

Loose or corroded
battery cables.

or

Bad batteries.

Overloaded output;

or

Shorted output.

Plug in AC power cord.

Reset breaker.

Reset breaker.

Wait for voltage to
stabilize.

Wait approximately
one minute for
synchronization.

Reset breaker.

*Replace fuse.

*Clean and tighten
battery cables.

*Replace batteries.

Reduce load.

Check load for short.

No Output Power:
"LINE PRESENT" OFF
"LINE FAILURE" OFF

Unit does not resume
LINE
PRESENT operation
when power returns:
"LINE PRESENT" ON
(or flashing)
"LINE FAILURE" ON

"SERVICE" LED ON

Incorrect output
voltage:
"LINE PRESENT" ON
"LINE FAILURE" OFF
"OVERLOAD" ON

* ITEMS TO BE PERFORMED ONLY BY A QUALIFIED TECHNICIAN

Advertising