2 external modem configuration – Alpha Technologies CFR 1500, CFR 1500RM User Manual

Page 35

Advertising
background image

29

4.2

External Modem Configuration

Specifications

Modem:

USRobotics Sportster external modem, 1200, 9600, 19.2K, or
28.8K baud or any Hayes compatible modem (may require a
custom initialization string)

Cable:

Standard null-modem cable, DE-9 male to DB-25 male. See
section “2.6 RS–232 Communications Options.”

RS–232 Speed:

1200 Baud (between CFR and modem)

RS–232 signals:

Rx, Tx, and GND

Handshaking:

None: neither hardware (RTS/CTS) nor software (XON/XOFF)
are required.

Cmd Menu Text

Options

Default

52

External Modem setup

(

displays 520-528 menu items)

520 Enable Automatic Alarms

(

YES / NO)

NO

521 Enable Remote Access

(

YES / NO)

NO

522 Set Alarm Actions

UPS000 - power up

(

NONE / DIAL1 / DIAL2)

DIAL1

UPS001 - input out of tolerance

(

NONE / DIAL1 / DIAL2)

DIAL1

UPS002 - input blackout
UPS003 - inverter on
UPS004 - line mode
UPS005 - low battery warning

(

NONE / DIAL1 / DIAL2)

DIAL1

UPS016 - battery OK
UPS006 - low battery shutdown

(

NONE / DIAL1 / DIAL2)

DIAL1

UPS007 - overload

(

NONE / DIAL1 / DIAL2)

DIAL1

UPS008 - load OK
UPS009 - temperature high
UPS010 - temperature OK
UPS011 - service required

(

NONE / DIAL1 / DIAL2)

DIAL1

UPS012 - UPS malfunction
UPS013 - self-test started (Inv. on)
UPS014 - self-test passed (line mode)
UPS015 - self-test failed

(

NONE / DIAL1 / DIAL2)

DIAL1

UPS017 - output shuts down in HH:MM

(

NONE / DIAL1 / DIAL2)

DIAL1

UPS018 - output shutdown
UPS019 - output restored

523 Set Inverter On Alarm Delay

0-5 minutes

0 minutes

524 Set DIAL1 Phone Number

20 char

ATDT 234-5678

525 Set DIAL2 Phone Number

20 char

ATDT 1-123-456-7890

526 Set Location ID

20 char

CFR UPS in Rm 123

527 Set Custom Modem Init command

30 char

ATDT X4Q0V1 &H0&R1&I0&B1

528 Set Remote Hang Up Time

1-100 minutes

2 minutes

4. OPERATION

44

5.5

System Parameters

The “SYSTEM PARAMETERS” screen provides UPS battery temperature

information and manual initiation and termination of SELF TEST.

5.4

Menu Commands Overview

, continued

Calibrating the CFR

The CFR UPS may be calibrated using two sets of parameters - Maintenance

Parameters (commands “70” to “79”) and Service Parameters (commands “80” to
“89”). Maintenance parameters allow you to customize the CFR detection and
warning levels. There should be no need to change these setting unless wider or
narrower detection tolerances are required.

Transmitting Unsolicited Alarms

The UPS can automatically transmit alarm messages (in ASCII format) to

notify a status change or a power problem as it occurs. You can enable or disable
this option by using commands “510” and “509” respectively.

5. RS-232 TERMINAL COMMUNICATION

12

11

1

Battery Temperature

Displayed in degrees C, Ambient Temperature is measured inside

the UPS in t he vicinity of the battery compartment.

Start Test

Self Test can be initiated by selecting this menu. The test duration

default is 60 seconds.

Stop Test

Self Test can be terminated prior to the full duration of the test run

time.