13 event descriptions – Alpha Technologies CFR 1500, CFR 1500RM User Manual

Page 65

Advertising
background image

14

Fig. 8

External Alarms Connector Pin-out

(with Factory installed EPO Switch Option)

2.5

Communication / Interface Options

, continued

2. FEATURES

Pin 1

N.C.

Pin out: (RJ-45 connector, Female)

1.

LINE FAIL, COM contact

2.

LINE FAIL, N. C. contact

3.

LINE FAIL, N. O. contact

4.

LOW BATTERY, N. O. contacts

5.

LOW BATTERY, COM contacts

6.

LOW BATTERY, N. C. contacts

7.
8.

Line Present

N.C.

Battery OK

N.O.

N.C. = Normally Closed
N.O. = Normally Open

EPO

Emergency

Power OFF

Option

Emergency UPS Shutdown
Switch (Wall Mounted).
NOTE: Cable length must not
exceed 100 feet. Use twisted
or shielded wire.

External Alarms Connector,

continued

Pin out: (RJ-45 connector, centered key)

59

5. RS-232 TERMINAL COMMUNICATION

5.13 Event Descriptions (Alarms)

There are 6 alarm groups which upon activation will be displayed at the

end of the opening menu. These are:

INPUT:
BATTERY:
OUTPUT:
ENVIRONMENTAL:
SERVICE1:
SERVICE2:

The following lists the mnemonics and description for each alarm group:

INPUT:
FREQ_LO

- input line frequency low

FREQ_HI

- input line frequency high

GLITCH

- input line glitch has been detected

SPIKE

- input line spike has been detected

SAG

- input line sag has been detected

SURGE

- input line surge has been detected

BROWNOUT

- input line brownout has been detected

SLOW_SURGE

- input line slow surge has been detected

BLACKOUT

- input line blackout has been detected

BATTERY:
LO_BAT_SHTDWN - battery voltage shutdown level detected
LO_BAT_WARN

- battery voltage low warning level detected

BAT_VOLT_HI

- battery over voltage level detected *

FAIL_SELF_TEST

- failed self test *

BATT_FLT

- battery fault has been detected *

OUTPUT:
VOLT_LO

- output voltage low has been detected

VOLT_HI

- output voltage high has been detected

PWR_OVLD

- output power overload has been detected

VA_OVLD

- output VA overload has been detected

OVER_V_FLT

- output over voltage fault has been detected *

SHORT_CCT

- output short circuit has been detected *

ENVIRONMENTAL:
AMB_TEMP_HI

- high internal ambient temperature detected *

SERVICE 1:
SERV CODE 1

- phase lock loop failure has been detected *

SERVICE 2:
SERV CODE 2

- micro software reset has been activated

SERV CODE 3

- micro hardware reset has been activated

SERV CODE 4

- power board EEPROM fault has been detected *

SERV CODE 5

- power board hardware fault has been detected *

SERV CODE 6

- neg DC supply rail has been detected *

EMGNCY POFF

- emergency power off has been activated

OUTV SHTDWN

- remote shutdown feature is currently active

*(service light alarm)