7 troubleshooting using the sid, 2 the cfr advantage, Communications and intelligence – Alpha Technologies CFR 1500, CFR 1500RM User Manual

Page 76: Self-test capabilities, Precise load and overload information, Generator ready, Safety, Introduction, Maintenance 6.7 troubleshooting using the sid

Advertising
background image

3

1.2

The CFR Advantage

, continued

COMMUNICATIONS AND INTELLIGENCE

Alpha's interchangeable Standard Interface Device and Intelligent Interface

Device allows your CFR to become an active part of your communications network
providing you with a variety of interface options.

SELF-TEST CAPABILITIES

The CFR has a built-in, self-test function that checks all critical areas of

the UPS, including the batteries, to ensure optimum performance. Whenever a
problem is detected, the UPS lights a “Service” indicator. Self-test is extremely
useful during troubleshooting and maintenance.

PRECISE LOAD AND OVERLOAD INFORMATION

The Alpha CFR provides vital load information to eliminate guess work

associated with matching the appropriate load to your unit. The Alpha CFR displays
the existing load, and whenever the load exceeds the rated output, an "Overload"
indicator is illuminated.

GENERATOR READY

The CFR UPS is equipped with a frequency sense circuit, along with a

constant slew frequency synchronization circuit, to provide trouble-free operation
with most standby generators.

SAFETY

Designed to meet or exceed the safety standards established by UL,

CSA and VDE, the Alpha CFR UPS is one of the safest, most reliable and versatile
uninterruptible power supplies available. Our commitment to safety and quality
engineering has not only established industry-wide safety standards, but has earned
Alpha Technologies international recognition as a leader in power protection
equipment.

1. INTRODUCTION

70

6. MAINTENANCE

6.7

Troubleshooting Using the SID

The OUTPUT LOAD LEDs, located on the front panel of the Standard Interface

Device, are designed to display UPS fault conditions once the unit has detected an
internal problem, indicated by the SERVICE LED. This information provided by the
LEDs is extremely useful during troubleshooting and maintenance. If the UPS is equipped
with an IID, refer to its operator’s manual for further troubleshooting information.

If your UPS SERVICE LED is ON, press and hold the ALARM OFF switch for

approximately 3 seconds. The OUTPUT LOAD LED's indicate:

Fig. 32

Standard Interface Device (Troubleshooting)

LOW BATTERY

WARN

ING

LOW

BATTERY

SHUTDOWN

L INE PRE SENT

L INE FA ILURE

SERVICE

TEST

ALPHA

TECHNOLOGIES

ALARM

OFF

OUTPUT LOAD

OVERLOAD
100 %
75 %
50 %
25 %

MANUAL

START

SERVICE LED

OUTPUT LOAD LEDs

ALARM OFF Switch

Standard Interface Device - Fault Indicators

LED

Flashing

Continuous

OVERLOAD

Not Applicable

Fast Detector / Low Sensitivity
Setting Active

100%

PLL Fault

High Ambient Temperature

75%

Output Voltage High

Output Voltage Short Circuit

50%

PWR BRD Fault

PWR BRD EPROM Failure

or -5 VDC Failure

25%

Self-Test Failure

Battery Over-Voltage
or Charger Fault