Connecting the External Battery Pack

DANGER: There are hazardous voltages inside the battery packs. Use extreme cau-
tion. For more information on battery handling, see the safety instructions in the front of
this manual.

CAUTION:
1)
Verify the pack’s polarity and voltage at the connector before attaching the cable to
the unit.

2) When a pack or batteries have been in storage for more than 6 months, they should
be recharged for at least 24 hours and then thoroughly tested with a load before installa-
tion. If after charging, a battery’s voltage varies more than 0.3 VDC from the others, do
not use it.

Tools and Materials Required:

• DC voltmeter.

• Phillips screwdriver.

Procedure:

1

Verify the battery circuit breaker is switched off. Keep it off until after the unit has been

started with line power.

2

Loosen the cover plate and slide it up to expose the connector (Figures 2.5, 2.6).

3

Verify the correct DC voltage and polarity at the battery pack’s connector. It should be

between 48 to 53 VDC.

TIP: Wrong voltages or polarities could damage the unit or the battery pack.

4

Connect the pack’s ground wire to the unit’s ground connection.

5

Connect the pack’s connector to the unit’s battery connector.

Battery Pack Connection Finished