Installing the unit, Cfr 3000, 2 installing the unit – Alpha Technologies CFR 3000, CFR 3000RM User Manual

Page 19: How to unpack and install the unit (section 2.2), Tools and materials required, Procedure: 1

Advertising
background image

13

2

Installation

2.2

Installing the Unit

2.2.1: CFR 3000

TIP: The seismic brackets can be removed if they are not required by the local code or
you are not in an earthquake zone (See

5

).

Tools and Materials Required:

• Fork lift or other means of transporting heavy objects (up to 288 lbs./131 kg).

• Screwdriver or power screwdriver with a Philips bit.

15

/

16

inch socket wrench.

Procedure:

1

The unit is shipped attached to a pallet. Use a forklift to transport the unit and pallet to the

installation site.

2

Remove the packing from around the unit. Unbolt the unit from the pallet.

3

Slide the unit off the pallet as per the included instruction sheet (017–098–C3). Move the

unit to its final position.

4

If the seismic brackets are used:

The drawing below looks down unto the brackets and the floor:

Mark the position on the floor where the unit will be secured by using the bracket as a tem-
plate. Drill holes and secure using the appropriate anchor bolts.

0.781 inch diameter for mounting heavy duty anchor bolts

(Hilti #665927 (HSL M12/25)).

0.562 inch diameter for mounting 0.5 inch anchor bolts.

Advertising