Low battery shutdown, Test, Line synchronization – Alpha Technologies CFR 3000, CFR 3000RM User Manual

Page 39: Push buttons alarm off, Manual start

Advertising
background image

33

3

Operation

Low Battery Shutdown

This red LED turns on when the battery voltage is 12% below nominal. The unit automati-
cally shuts itself down and no longer provides power to the loads to prevent
overdischarge damage to the batteries.

Test

This yellow LED shows the unit is in self test mode (Section 3.3). If it fails the test, the
Service LED is on and the unit defaults to Line Present operation. You should do trouble-
shooting as shown in Sections 3.4 or 5.2.

TIP: At start-up, this LED flashes for about 5 to 15 seconds.

Line Synchronization

If both the:

Line Power

Line Failure

LEDs are on, the unit is synchronizing its output with the input before starting Line
Present operation. This takes about 15 seconds.

Push Buttons

Alarm Off

This turns off most audible alarms. The alarm is off until another alarm occurs.

TIP: Some alarms, such as Line Failure, cannot be turned off and will continue to sound
every 20 seconds. If the Service LED is on, press and hold down the Alarm Off switch
and note which Output Load LEDs turns on or flashes (Section 3.4).

Manual Start

This starts the unit with battery power when line power is absent or unqualified.

It can also be used as a self test. If the Line Present LED is on, press it for 5 seconds.
This tests the inverter and batteries for one minute by providing backup battery power to
the loads, returning to line present mode when done.

3.5 Controlling the Unit with the Standard Interface Device (SID) (Continued)