Configuring the input/output voltage, 5 configuring the input/output voltage, How to change the unit’s input and output volt – Alpha Technologies CFR 3000, CFR 3000RM User Manual

Page 73: Ages (section 5.5), Tools and materials required, Procedure: 1

Advertising
background image

67

5

Maintenance

5.5

Configuring the Input/Output Voltage

The unit is factory configured to your input/output voltage specifications.

• Units configured only for 120 VAC input and output voltage need a new high voltage

board installed before re-configuring the input or output voltage. Contact Alpha Technolo-
gies customer service department.

• Units configured for 230 VAC, 50 Hz input and output cannot be re-configured.

• Units configured for 208 VAC or 240 VAC input voltage can be re-configured to 208 VAC

or 240 VAC input voltage.

• Units configured for 120/208 VAC output or 120/240 VAC output can be re-configured to

120/208 VAC or 120/240 VAC output.

DANGER: Lethal levels of voltages and currents are inside the unit when it is con-
nected to line and battery power. The Input and Battery circuit breakers on the rear
panel must be switched off before starting this procedure.

Tools and Materials Required:

• Phillips and Slotted Screwdrivers.

Procedure:

1

Turn off all loads. Make sure the Input and Battery circuit breakers on the rear panel are

switched off.

2

For the CFR 3000, remove the front panel and the cover as described in Step 1 of Section

5.4. Find the high voltage board labeled as “700–226–XX” (Figure 5.4).

Figure 5.4

High Voltage Board in CFR 3000