Testing the unit, 3 testing the unit, Loads connected (section 3.3) – Alpha Technologies CFR 3000, CFR 3000RM User Manual

Page 36: How to start the unit’s self test (section 3.3), Do a self test (section 3.3), Procedure: 1, Self test finished, 3operation 30

Advertising
background image

3

Operation

30

3.3 Testing the Unit

The self test confirms the unit can switch from line to backup battery power and back without
interrupting power to the loads. It takes about one minute to run.

Before starting:

• The Battery circuit breaker must be on.

• The control panel’s Line Present LED must be on.

Procedure:

1

Press the Manual Start button down for 5

seconds.

During the test, the Test, Line Present and
Line Failure LEDs are on for about one
minute.

2

If a fault is found, the unit defaults to Line

Present operation without interrupting the
output. The Service LED turns on. Do
troubleshooting (Sections 3.4, 5.2).

TIP: The unit cannot provide backup battery
power when the Service LED is on.

Self Test Finished

ALARM
OFF

MANUAL
START

OUTPUT LOAD

OVERLOAD

100%

75%

50%

25%

LINE PRESENT

LINE FAILURE

SERVICE

LOW BATTERY
WARNING

LOW BATTERY
SHUTDOWN

TEST