Connecting the lan port, 6 connecting the lan port, Lan interface connector – Alpha Technologies CFR 3000, CFR 3000RM User Manual

Page 28: This db–9 port provides dry contact, Status monitoring and output shutdown, Capability via lan communication (sec, Tion 2.7), How to connect the lan port (section 2.7), 7 connecting the lan port, 2installation 22

Advertising
background image

2

Installation

22

2.7

Connecting the LAN Port

The unit can be remotely monitored and shutdown with the unit’s DB–9 LAN port (Figure 2.9).

Two dry contacts provide line failure and low battery information. A connection to the unit’s mi-
croprocessor shuts down the unit’s output. The shutdown delay, duration and recovery is con-
trolled via RS–232 commands (Section 4.5).

Figure 2.9

Wiring the LAN Port

8

7

6

5

4

3

2

1

Output

Shutdown

N.O. Line

Failure

N.O. Low

Battery

UPS Internal

UPS External

9

GND

+12 VDC

5 mA (Max)

Common

1

2

3

4

5

6

7

8

9

Low

Battery

Not

Connected

Not

Connected

+12 VDC

5 mA (Max)

Output

Shutdown

Line

Fail

Common

Not

Connected

Advertising